Request for Tenders dated 25/03/2021 for the supply of a High Temperature 1MW Air Source Heat Pump to University College Dublin
[Fileref]:
UCDOPP5087
Tenders are sought for the supply, delivery, provision of detailed offloading, installation and assembly guidance and attendance at site for electrical and Building Management System (BMS) connection witnessing and commissioning of high temperature, high efficiency 1MW Air to Water Heat Pump (ASHP), with a thermal output of 1,000kW at 7 °C Outside Air Temperature (OAT) capable of operating at a flow temperature of 75°C. It’s lower operating temperature limit will be -7degC OAT.
[ValueExclVat]:
792500.00
EUR